Contactor, 3p+1N/O, 11kW/400V/AC3 | ||
Part no. | DILM25-10(24V60HZ) | |
Catalog No. | 277123 | |
Eaton Catalog No. | XTCE025C10B6 | |
General | |||
Standards |
IEC/EN 60947, VDE 0660, UL, CSA | ||
Lifespan, mechanical |
|||
AC operated |
Operations | x 106 | 10 |
DC operated |
Operations | x 106 | 10 |
Operating frequency, mechanical |
|||
AC operated |
Operations/h | 5000 | |
DC operated |
Operations/h | 5000 | |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
||
Ambient temperature |
|||
Enclosed |
°C | - 25 - 40 | |
Storage |
°C | - 40 - 80 | |
Mechanical shock resistance (IEC/EN 60068-2-27) |
|||
Half-sinusoidal shock, 10 ms |
|||
Main contacts |
|||
N/O contact |
g | 10 | |
Auxiliary contacts |
|||
N/O contact |
g | 7 | |
N/C contact |
g | 5 | |
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted |
|||
Half-sinusoidal shock, 10 ms |
|||
Main contacts |
|||
N/O contact |
g | 6.9 | |
Auxiliary contacts |
|||
N/O contact |
g | 5.3 | |
N/C contact |
g | 3.5 | |
Degree of Protection |
IP00 | ||
Protection against direct contact when actuated from front (EN 50274) |
Finger and back-of-hand proof | ||
Weight |
|||
AC operated |
kg | 0.42 | |
DC operated |
kg | 0.48 | |
Terminal capacity main cable |
|||
Solid |
mm2 |
1 x (0.75 - 16) 2 x (0.75 - 10) |
|
Flexible with ferrule |
mm2 |
1 x (0.75 - 16) 2 x (0.75 - 10) |
|
Stranded |
mm2 | 1 x 16 | |
Solid or stranded |
AWG | 18 - 6 | |
Stripping length |
mm | 10 | |
Main cable connection screw/bolt |
M5 | ||
Tightening torque |
Nm | 3.2 | |
Terminal capacity control circuit cables |
|||
Solid |
mm2 |
1 x (0.75 - 4) 2 x (0.75 - 4) |
|
Flexible with ferrule |
mm2 |
1 x (0.75 - 1.5) 2 x (0.75 - 1.5) |
|
Solid or stranded |
AWG | 18 - 14 | |
Control circuit cable connection screw/bolt |
M3.5 | ||
Tightening torque |
Nm | 1.2 | |
Tool |
|||
Main cable |
|||
Pozidriv screwdriver |
Size | 2 | |
Standard screwdriver |
mm |
0.8 x 5.5 1 x 6 |
|
Control circuit cables |
|||
Pozidriv screwdriver |
Size | 2 | |
Standard screwdriver |
mm |
0.8 x 5.5 1 x 6 |
|
Terminal capacity control circuit cables |
|||
Solid |
mm2 |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
|
Flexible |
mm2 |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
|
Flexible with ferrule |
mm2 |
1 x (0.75 - 1.5) 2 x (0.75 - 1.5) |
|
Solid or stranded |
AWG | 18 - 14 | |
Tool |
|||
Stripping length |
mm | 10 | |
Screwdriver blade width |
mm | 3.5 | |
Main conducting paths | |||
Rated impulse withstand voltage |
Uimp | V AC | 8000 |
Overvoltage category/pollution degree |
III/3 | ||
Rated insulation voltage |
Ui | V AC | 690 |
Rated operational voltage |
Ue | V AC | 690 |
Safe isolation to EN 61140 |
|||
between coil and contacts |
V AC | 440 | |
between the contacts |
V AC | 440 | |
Making capacity (p.f. to IEC/EN 60947) |
|||
Up to 690 V | A | 350 | |
Breaking capacity |
|||
220 V 230 V |
A | 250 | |
380 V 400 V |
A | 250 | |
500 V |
A | 250 | |
660 V 690 V |
A | 150 | |
Short-circuit rating |
|||
Short-circuit protection maximum fuse |
|||
Type “2” coordination |
|||
400 V |
gG/gL 500 V | A | 35 |
690 V |
gG/gL 690 V | A | 35 |
Type “1” coordination |
|||
400 V |
gG/gL 500 V | A | 100 |
690 V |
gG/gL 690 V | A | 50 |
AC | |||
AC-1 |
|||
Rated operational current |
|||
Conventional free air thermal current, 3 pole, 50 - 60 Hz |
|||
Open |
|||
at 40 °C |
Ith =Ie | A | 45 |
at 50 °C |
Ith =Ie | A | 43 |
at 55 °C |
Ith =Ie | A | 42 |
at 60 °C |
Ith =Ie | A | 40 |
enclosed |
Ith | A | 36 |
Conventional free air thermal current, 1 pole |
|||
open |
Ith | A | 100 |
enclosed |
Ith | A | 90 |
AC-3 |
|||
Rated operational current |
|||
Open, 3-pole: 50 – 60 Hz |
|||
220 V 230 V |
Ie | A | 25 |
240 V |
Ie | A | 25 |
380 V 400 V |
Ie | A | 25 |
415 V |
Ie | A | 25 |
440V |
Ie | A | 25 |
500 V |
Ie | A | 25 |
660 V 690 V |
Ie | A | 15 |
380 V 400 V |
Ie | A | 25 |
Motor rating |
P | kWh | |
220 V 230 V |
P | kW | 7.5 |
240V |
P | kW | 8.5 |
380 V 400 V |
P | kW | 11 |
415 V |
P | kW | 14.5 |
440 V |
P | kW | 15.5 |
500 V |
P | kW | 17.5 |
660 V 690 V |
P | kW | 14 |
AC-4 |
|||
Open, 3-pole: 50 – 60 Hz |
|||
220 V 230 V |
Ie | A | 13 |
240 V |
Ie | A | 13 |
380 V 400 V |
Ie | A | 13 |
415 V |
Ie | A | 13 |
440 V |
Ie | A | 13 |
500 V |
Ie | A | 13 |
660 V 690 V |
Ie | A | 10 |
Motor rating |
P | kWh | |
220 V 230 V |
P | kW | 3.5 |
240 V |
P | kW | 4 |
380 V 400 V |
P | kW | 6 |
415 V |
P | kW | 6.5 |
440 V |
P | kW | 7 |
500 V |
P | kW | 8 |
660 V 690 V |
P | kW | 8.5 |
DC | |||
Rated operational current, open |
|||
DC-1 |
|||
60 V |
Ie | A | 40 |
110 V |
Ie | A | 40 |
220 V |
Ie | A | 40 |
440 V |
Ie | A | 2.9 |
DC-3 |
|||
60 V |
Ie | A | 35 |
110 V |
Ie | A | 35 |
220 V |
Ie | A | 10 |
440 V |
Ie | A | 0.6 |
DC-5 |
|||
60 V |
Ie | A | 35 |
110 V |
Ie | A | 35 |
220 V |
Ie | A | 10 |
440 V |
Ie | A | 0.6 |
Current heat loss | |||
3 pole, at Ith (60°) |
W | 9.6 | |
Current heat loss at Ie to AC-3/400 V |
W | 3.8 | |
Impedance per pole |
mΩ | 2 | |
Magnet systems | |||
Voltage tolerance |
|||
AC operated |
Pick-up | x Uc | 0.8 - 1.1 |
Drop-out voltage AC operated |
Drop-out | x Uc | 0.3 - 0.6 |
DC operated |
Pick-up | x Uc | 0.7 - 1.2 |
DC operated |
Drop-out | x Uc | 0.15 - 0.6 |
Notes |
at least smoothed two-phase bridge rectifier or three-phase rectifier | ||
Power consumption of the coil in a cold state and 1.0 x Uc |
|||
50 Hz |
Pick-up | VA | 52 |
50 Hz |
Sealing | VA | 7.1 |
50 Hz |
Sealing | W | 2.1 |
60 Hz |
Pick-up | VA | 67 |
60 Hz |
Sealing | VA | 8.7 |
60 Hz |
Sealing | W | 2.6 |
50/60 Hz |
Pick-up | VA |
62 58 |
50/60 Hz |
Sealing | VA |
9.1 6.5 |
50/60 Hz |
Sealing | W |
2.5 2 |
DC operated |
Pick-up | W | 12 |
DC operated |
Sealing | W | 0.5 |
Duty factor |
% DF | 100 | |
Changeover time at 100 % UC (recommended value) |
|||
Main contacts |
|||
AC operated |
|||
Closing delay |
ms | 16 - 22 | |
Opening delay |
ms | 8 - 14 | |
DC operated |
ms | ||
Closing delay |
ms | 47 | |
Opening delay |
ms | 30 | |
Arcing time |
ms | 10 | |
Lifespan, mechanical; Coil 50/60 Hz |
x 106 | Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general” | |
Electromagnetic compatibility (EMC) | |||
Emitted interference |
to EN 60947-1 | ||
Interference immunity |
to EN 60947-1 | ||
Rating data for approved types | |||
Switching capacity |
|||
Maximum motor rating |
|||
Three-phase |
|||
200 V 208 V |
HP | 7.5 | |
230 V 240 V |
HP | 5 | |
460 V 480 V |
HP | 15 | |
575 V 600 V |
HP | 20 | |
Single-phase |
|||
115 V 120 V |
HP | 2 | |
230 V 240 V |
HP | 5 | |
General use |
A | 40 | |
Auxiliary contacts |
|||
Pilot Duty |
|||
AC operated |
A600 | ||
DC operated |
P300 | ||
General Use |
|||
AC |
V | 600 | |
AC |
A | 10 | |
DC |
V | 250 | |
DC |
A | 1 | |
Short Circuit Current Rating |
SCCR | ||
Basic Rating |
|||
SCCR |
kA | 5 | |
max. Fuse |
A | 125 | |
max. CB |
A | 125 | |
480 V High Fault |
|||
SCCR (fuse) |
kA | 10/100 | |
max. Fuse |
A | 125/70 Class J | |
SCCR (CB) |
kA | 10/65 | |
max. CB |
A | 50/32 | |
600 V High Fault |
|||
SCCR (fuse) |
kA | 10/100 | |
max. Fuse |
A | 125/100 Class J | |
SCCR (CB) |
kA | 10/22 | |
max. CB |
A | 50/32 | |
Special Purpose Ratings |
|||
Electrical Discharge Lamps (Ballast) |
|||
480V 60Hz 3phase, 277V 60Hz 1phase |
A | 40 | |
600V 60Hz 3phase, 347V 60Hz 1phase |
A | 40 | |
Incandescent Lamps (Tungsten) |
|||
480V 60Hz 3phase, 277V 60Hz 1phase |
A | 40 | |
600V 60Hz 3phase, 347V 60Hz 1phase |
A | 40 | |
Resistance Air Heating |
|||
480V 60Hz 3phase, 277V 60Hz 1phase |
A | 40 | |
600V 60Hz 3phase, 347V 60Hz 1phase |
A | 40 | |
Refrigeration Control (CSA only) |
|||
LRA 480V 60Hz 3phase |
A | 240 | |
FLA 480V 60Hz 3phase |
A | 40 | |
LRA 600V 60Hz 3phase |
A | 180 | |
FLA 600V 60Hz 3phase |
A | 30 | |
Definite Purpose Ratings (100,000 cycles acc. to UL 1995) |
|||
LRA 480V 60Hz 3phase |
A | 150 | |
FLA 480V 60Hz 3phase |
A | 25 | |
Elevator Control |
|||
200V 60Hz 3phase |
HP | 3 | |
200V 60Hz 3phase |
A | 11 | |
240V 60Hz 3phase |
HP | 5 | |
240V 60Hz 3phase |
A | 15.2 | |
480V 60Hz 3phase |
HP | 10 | |
480V 60Hz 3phase |
A | 14 | |
600V 60Hz 3phase |
HP | 15 | |
600V 60Hz 3phase |
A | 17 |
Product Standards | IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking | ||
UL File No. | E29096 | ||
UL Category Control No. | NLDX | ||
CSA File No. | 012528 | ||
CSA Class No. | 2411-03, 3211-04 | ||
North America Certification | UL listed, CSA certified | ||
Specially designed for North America | No |