Datasheet - NZM2/3-XUHIV380-440AC

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Undervoltage release, 380-440VAC, +2early N/O
Part no.  NZM2/3-XUHIV380-440AC
Catalog No.  259594
 
 
Similar to illustration
 

Delivery program
Product range
    Accessories
Accessories
    Undervoltage release
Accessories
    Undervoltage release with early-make auxiliary contact
Standard/Approval
    UL/CSA, IEC
Construction size
    NZM2/3
Description
    Undervoltage release with 2 early-make auxiliary contacts, e.g., for early-make connection of undervoltage release in main switch applications, as well as for interlock and load shedding circuits.
For use with emergency switching off devices in conjunction with Emergency switching off button.
When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.
Early make of auxiliary contacts on switching on and off (manual operation): approx. 20 ms
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
Cannot be used in conjunction with NZM...-XR... remote operator.
Connection type
    With bolt connection
Auxiliary contacts
    with 2 early-make auxiliary contacts
Rated control voltage
Us V 380 - 440 V 50/60 Hz
For use with
    NZM2(-4), N(S)2(-4)
NZM3(-4), N(S)3(-4)
Technical data
Undervoltage release
Rated control voltage
Us V  
AC
Us V AC 24 - 600
DC
Us V DC 12 - 250
Rated control voltage
Us V 380 - 440 V 50/60 Hz
Operating range
     
Drop-out voltage
  x Us 0.35 - 0.7
Pick-up voltage
x Uc   0.85 - 1.1
Power consumption
     
AC
     
Pick-up AC
  VA 1.5
Sealing AC
  VA 1.5
DC
  x Us  
Pick-up DC
  W 0.8
Sealing DC
  W 0.8
Maximum opening delay (response time until opening of the main contacts)
  ms 19
Minimum command time
  ms 10 - 15
Terminal capacities
Solid or flexible conductor, with ferrule
  mm2 1 x (0,75 - 2,5)
2 x (0,75 - 2,5)
 
  AWG 1 x (18 … 14)
2 x (18 … 14)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Under voltage coil (EC001022)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip (ecl@ss8.1-27-37-04-17 [AKF015010])
Rated control supply voltage Us at AC 50HZ
  V 380 - 440
Rated control supply voltage Us at AC 60HZ
  V 380 - 440
Rated control supply voltage Us at DC
  V 0 - 0
Voltage type for actuating
    AC
Type of electric connection
    Screw connection
Number of contacts as normally open contact
    2
Number of contacts as normally closed contact
    0
Number of contacts as change-over contact
    0
Delayed
    No
Suitable for power circuit breaker
    Yes
Suitable for off-load switch
    Yes
Suitable for motor safety switch
    No
Suitable for overload relay
    No
Approvals
Product Standards     UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No.     E140305
UL Category Control No.     DIHS
CSA File No.     022086
CSA Class No.     1437-01
North America Certification     UL listed, CSA certified