Standards |
|
|
IEC/EN 60947, VDE 0660, UL, CSA
|
Lifespan, mechanical |
|
|
|
AC operated |
Operations |
x 106
|
10
|
DC operated |
Operations |
x 106
|
10
|
Operating frequency, mechanical |
|
|
|
AC operated |
Operations/h |
|
3600
|
DC operated |
Operations/h |
|
3600
|
Climatic proofing |
|
|
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
|
Ambient temperature |
|
|
|
Open |
|
°C |
-25
-
+60
|
Enclosed |
|
°C |
- 25
-
40
|
Storage |
|
°C |
- 40
-
80
|
Mounting position |
|
|


|
Mechanical shock resistance (IEC/EN 60068-2-27) |
|
|
|
Half-sinusoidal shock, 10 ms |
|
|
|
Main contacts |
|
|
|
N/O contact |
|
g |
10
|
Auxiliary contacts |
|
|
|
N/O contact |
|
g |
7
|
N/C contact |
|
g |
5
|
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted |
|
|
|
Half-sinusoidal shock, 10 ms |
|
|
|
Main contacts |
|
|
|
N/O contact |
|
g |
10
|
Auxiliary contacts |
|
|
|
N/O contact |
|
g |
7
|
N/C contact |
|
g |
5
|
Degree of Protection |
|
|
IP00
|
Protection against direct contact when actuated from front (EN 50274) |
|
|
Finger and back-of-hand proof
|
Weight |
|
|
|
AC operated |
|
kg |
2
|
DC operated |
|
kg |
2.1
|
Terminal capacity main cable |
|
|
|
Flexible with ferrule |
|
mm2 |
1 x (10 - 95) 2 x (10 - 70)
|
Stranded |
|
mm2
|
1 x (16 - 95) 2 x (16 - 70)
|
Solid or stranded |
|
AWG |
8…3/0
|
Flat conductor |
Lamellenzahl x Breite x Dicke |
mm |
2 x (6 x 16 x 0.8)
|
Main cable connection screw/bolt |
|
|
M10
|
Tightening torque |
|
Nm |
14
|
Terminal capacity control circuit cables |
|
|
|
Solid |
|
mm2 |
1 x (0.75 - 4) 2 x (0.75 - 4)
|
Flexible with ferrule |
|
mm2 |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5)
|
Solid or stranded |
|
AWG |
18 - 14
|
Control circuit cable connection screw/bolt |
|
|
M3.5
|
Tightening torque |
|
Nm |
1.2
|
Tool |
|
|
|
Main cable |
|
|
|
Hexagon socket-head spanner |
SW |
mm |
5
|
Control circuit cables |
|
|
|
Pozidriv screwdriver |
|
Size |
2
|
Standard screwdriver |
|
mm |
0.8 x 5.5 1 x 6
|
Rated impulse withstand voltage |
Uimp |
V AC |
8000
|
Overvoltage category/pollution degree |
|
|
III/3
|
Rated insulation voltage |
Ui |
V AC |
690
|
Rated operational voltage |
Ue |
V AC |
690
|
Safe isolation to EN 61140 |
|
|
|
between coil and contacts |
|
V AC |
690
|
between the contacts |
|
V AC |
690
|
Making capacity (p.f. to IEC/EN 60947) |
|
|
|
|
Up to 690 V |
A |
1330
|
Breaking capacity |
|
|
|
220 V 230 V |
|
A |
950
|
380 V 400 V |
|
A |
950
|
500 V |
|
A |
950
|
660 V 690 V |
|
A |
800
|
Short-circuit rating |
|
|
|
Short-circuit protection maximum fuse |
|
|
|
Type “2” coordination |
|
|
|
400 V |
gG/gL 500 V |
A |
160
|
690 V |
gG/gL 690 V |
A |
160
|
Type “1” coordination |
|
|
|
400 V |
gG/gL 500 V |
A |
250
|
690 V |
gG/gL 690 V |
A |
200
|
AC-1 |
|
|
|
Rated operational current |
|
|
|
Conventional free air thermal current, 3 pole, 50 - 60 Hz |
|
|
|
Open |
|
|
|
at 40 °C |
Ith =Ie |
A |
130
|
at 50 °C |
Ith =Ie |
A |
125
|
at 55 °C |
Ith =Ie |
A |
115
|
at 60 °C |
Ith =Ie |
A |
110
|
enclosed |
Ith
|
A |
100
|
Conventional free air thermal current, 1 pole |
|
|
|
open |
Ith
|
A |
275
|
enclosed |
Ith
|
A |
250
|
AC-3 |
|
|
|
Rated operational current |
|
|
|
Open, 3-pole: 50 – 60 Hz |
|
|
|
220 V 230 V |
Ie |
A |
95
|
240 V |
Ie |
A |
95
|
380 V 400 V |
Ie |
A |
95
|
415 V |
Ie |
A |
95
|
440V |
Ie |
A |
95
|
500 V |
Ie |
A |
95
|
660 V 690 V |
Ie |
A |
80
|
380 V 400 V |
Ie |
A |
95
|
Motor rating |
P |
kWh |
|
220 V 230 V |
P |
kW |
30
|
240V |
P |
kW |
32
|
380 V 400 V |
P |
kW |
45
|
415 V |
P |
kW |
57
|
440 V |
P |
kW |
60
|
500 V |
P |
kW |
70
|
660 V 690 V |
P |
kW |
75
|
AC-4 |
|
|
|
Open, 3-pole: 50 – 60 Hz |
|
|
|
220 V 230 V |
Ie
|
A |
50
|
240 V |
Ie
|
A |
50
|
380 V 400 V |
Ie
|
A |
50
|
415 V |
Ie
|
A |
50
|
440 V |
Ie
|
A |
50
|
500 V |
Ie
|
A |
50
|
660 V 690 V |
Ie
|
A |
37
|
Motor rating |
P |
kWh |
|
220 V 230 V |
P |
kW |
16
|
240 V |
P |
kW |
17
|
380 V 400 V |
P |
kW |
26
|
415 V |
P |
kW |
30
|
440 V |
P |
kW |
32
|
500 V |
P |
kW |
36
|
660 V 690 V |
P |
kW |
35
|
Rated operational current, open |
|
|
|
DC-1 |
|
|
|
60 V |
Ie
|
A |
110
|
110 V |
Ie
|
A |
110
|
220 V |
Ie
|
A |
70
|
440 V |
Ie
|
A |
4.5
|
DC-3 |
|
|
|
60 V |
Ie
|
A |
110
|
110 V |
Ie
|
A |
110
|
220 V |
Ie
|
A |
35
|
440 V |
Ie
|
A |
1
|
DC-5 |
|
|
|
60 V |
Ie
|
A |
110
|
110 V |
Ie
|
A |
110
|
220 V |
Ie
|
A |
35
|
440 V |
Ie
|
A |
1
|
3 pole, at Ith (60°) |
|
W |
18.9
|
Current heat loss at Ie to AC-3/400 V |
|
W |
12.6
|
Impedance per pole |
|
mΩ |
0.6
|
Voltage tolerance |
|
|
|
AC operated |
Pick-up |
x Uc |
0.8
-
1.1
|
Drop-out voltage AC operated |
Drop-out |
x Uc
|
0.3
-
0.6
|
DC operated |
Pick-up |
x Uc
|
0.7
-
1.2
|
DC operated |
Drop-out |
x Uc
|
0.15
-
0.6
|
Notes |
|
|
at least smoothed two-phase bridge rectifier or three-phase rectifier
|
Power consumption of the coil in a cold state and 1.0 x Uc |
|
|
|
50 Hz |
Pick-up |
VA |
310
|
50 Hz |
Sealing |
VA |
26
|
50 Hz |
Sealing |
W |
5.8
|
60 Hz |
Pick-up |
VA |
345
|
60 Hz |
Sealing |
VA |
30
|
60 Hz |
Sealing |
W |
7.1
|
50/60 Hz |
Pick-up |
VA |
372 328
|
50/60 Hz |
Sealing |
VA |
37.1 22.6
|
50/60 Hz |
Sealing |
W |
7.5 6.1
|
DC operated |
Pick-up |
W |
90
|
DC operated |
Sealing |
W |
1.3
|
Duty factor |
|
% DF |
100
|
Changeover time at 100 % UC (recommended value) |
|
|
|
Main contacts |
|
|
|
AC operated |
|
|
|
Closing delay |
|
ms |
14
-
20
|
Opening delay |
|
ms |
9
-
14
|
DC operated |
|
ms |
|
Closing delay |
|
ms |
45
|
Opening delay |
|
ms |
34
|
Arcing time |
|
ms |
15
|
Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal). |
|
mA |
1
|
Lifespan, mechanical; Coil 50/60 Hz |
|
x 106 |
Mechanical lifespan at 50 Hz approx. 30% lower than under “General”
|
Emitted interference |
|
|
to EN 60947-1
|
Interference immunity |
|
|
to EN 60947-1
|
Switching capacity |
|
|
|
Maximum motor rating |
|
|
|
Three-phase |
|
|
|
200 V 208 V |
|
HP |
30
|
230 V 240 V |
|
HP |
15
|
460 V 480 V |
|
HP |
75
|
575 V 600 V |
|
HP |
100
|
Single-phase |
|
|
|
115 V 120 V |
|
HP |
7.5
|
230 V 240 V |
|
HP |
15
|
General use |
|
A |
125
|
Short Circuit Current Rating |
|
SCCR |
|
Basic Rating |
|
|
|
SCCR |
|
kA |
10
|
max. Fuse |
|
A |
600
|
max. CB |
|
A |
600
|
480 V High Fault |
|
|
|
SCCR (fuse) |
|
kA |
30/100
|
max. Fuse |
|
A |
300/300 Class J
|
SCCR (CB) |
|
kA |
65
|
max. CB |
|
A |
250
|
600 V High Fault |
|
|
|
SCCR (fuse) |
|
kA |
30/100
|
max. Fuse |
|
A |
300/300 Class J
|
SCCR (CB) |
|
kA |
30
|
max. CB |
|
A |
350
|
Special Purpose Ratings |
|
|
|
Electrical Discharge Lamps (Ballast) |
|
|
|
480V 60Hz 3phase, 277V 60Hz 1phase |
|
A |
100
|
600V 60Hz 3phase, 347V 60Hz 1phase |
|
A |
100
|
Incandescent Lamps (Tungsten) |
|
|
|
480V 60Hz 3phase, 277V 60Hz 1phase |
|
A |
100
|
600V 60Hz 3phase, 347V 60Hz 1phase |
|
A |
100
|
Resistance Air Heating |
|
|
|
480V 60Hz 3phase, 277V 60Hz 1phase |
|
A |
100
|
600V 60Hz 3phase, 347V 60Hz 1phase |
|
A |
100
|
Refrigeration Control (CSA only) |
|
|
|
LRA 480V 60Hz 3phase |
|
A |
540
|
FLA 480V 60Hz 3phase |
|
A |
90
|
LRA 600V 60Hz 3phase |
|
A |
420
|
FLA 600V 60Hz 3phase |
|
A |
70
|
Definite Purpose Ratings (100,000 cycles acc. to UL 1995) |
|
|
|
LRA 480V 60Hz 3phase |
|
A |
570
|
FLA 480V 60Hz 3phase |
|
A |
95
|
Elevator Control |
|
|
|
200V 60Hz 3phase |
|
HP |
20
|
200V 60Hz 3phase |
|
A |
62.1
|
240V 60Hz 3phase |
|
HP |
30
|
240V 60Hz 3phase |
|
A |
80
|
480V 60Hz 3phase |
|
HP |
60
|
480V 60Hz 3phase |
|
A |
77
|
600V 60Hz 3phase |
|
HP |
75
|
600V 60Hz 3phase |
|
A |
77
|