Motor-protective circuit-breaker, 3p, Ir=0.25-0.4A, screw connection | ||
Part no. | PKZM0-0,4 | |
Catalog No. | 072732 | |
Eaton Catalog No. | XTPRP40BC1NL | |
EL-Nummer (Norway) | 4355123 |
General | |||
Standards |
IEC/EN 60947, VDE 0660,UL, CSA | ||
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
||
Ambient temperature |
|||
Storage |
°C | - 40 - 80 | |
Open |
°C | -25 - +55 | |
Enclosed |
°C | - 25 - 40 | |
Mounting position |
![]() |
||
Direction of incoming supply |
as required | ||
Degree of protection |
|||
Device |
IP20 | ||
Terminations |
IP00 | ||
Protection against direct contact when actuated from front (EN 50274) |
Finger and back-of-hand proof | ||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 |
g | 25 | |
Altitude |
m | Max. 2000 | |
Terminal capacity main cable |
|||
Screw terminals |
|||
Solid |
mm2 |
1 x (1 - 6) 2 x (1 - 6) |
|
Flexible with ferrule to DIN 46228 |
mm2 |
1 x (1 - 6) 2 x (1 - 6) |
|
Solid or stranded |
AWG | 18 - 10 | |
Stripping length |
mm | 10 | |
Specified tightening torque for terminal screws |
|||
Main cable |
Nm | 1.7 | |
Control circuit cables |
Nm | 1 | |
Main conducting paths | |||
Rated impulse withstand voltage |
Uimp | V AC | 6000 |
Overvoltage category/pollution degree |
III/3 | ||
Rated operational voltage |
Ue | V AC | 690 |
Rated uninterrupted current = rated operational current |
Iu = Ie | A | 0.4 |
Rated frequency |
f | Hz | 40 - 60 |
Current heat loss (3 pole at operating temperature) |
W | 5.22 | |
Lifespan, mechanical |
Operations | x 106 | 0.1 |
Lifespan, electrical (AC-3 at 400 V) |
|||
Lifespan, electrical |
Operations | x 106 | 0.1 |
Max. operating frequency |
Ops/h | 40 | |
Short-circuit rating |
|||
AC |
|||
Other technical data (sheet catalogue) |
Schaltvermögen | ||
DC |
|||
Short-circuit rating |
kA | 60 | |
Notes |
up to 250 V | ||
Motor switching capacity |
|||
AC-3 (up to 690V) |
A | 0.4 | |
DC-5 (up to 250V) |
V | 0.4 (3 contacts in series) | |
Trip blocks | |||
Temperature compensation |
|||
to IEC/EN 60947, VDE 0660 |
°C | - 5 … 40 | |
Operating range |
°C | - 25 … 55 | |
Temperature compensation residual error for T > 40 °C |
≦ 0.25 %/K | ||
Setting range of overload releases |
x Iu | 0.6 - 1 | |
short-circuit release |
Basic device, fixed: 15.5 x Iu | ||
Short-circuit release tolerance |
± 20% | ||
Phase-failure sensitivity |
IEC/EN 60947-4-1, VDE 0660 Part 102 | ||
Rating data for approved types | |||
Switching capacity |
|||
Maximum motor rating |
|||
Three-phase |
|||
200 V 208 V |
HP | Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen. Angegebene Werte nach NEC Table 430-150 | |
230 V 240 V |
HP | Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen. Angegebene Werte nach NEC Table 430-150 | |
460 V 480 V |
HP | Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen. Angegebene Werte nach NEC Table 430-150 | |
575 V 600 V |
HP | Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen. Angegebene Werte nach NEC Table 430-150 | |
Short Circuit Current Rating, type E |
SCCR | ||
240 V |
kA | 65 | |
480 Y / 277 V |
kA | 65 | |
600 Y / 347 V |
kA | 50 | |
Accessories required |
BK25/3-PKZ0-E | ||
Short Circuit Current Rating, group protection |
SCCR | ||
600 V High Fault |
|||
SCCR (fuse) |
kA | 50 | |
max. Fuse |
A | 600 | |
SCCR (CB) |
kA | 50 | |
max. CB |
A | 600 |
Product Standards | IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking | ||
UL File No. | E36332 | ||
UL Category Control No. | NLRV | ||
CSA File No. | 165628 | ||
CSA Class No. | 3211-05 | ||
North America Certification | UL listed, CSA certified | ||
Specially designed for North America | No | ||
Suitable for | Branch circuit: Manual type E if used with terminal, or suitable for group installations |
IL03407010Z (AWA1210-2138) Motor-protective circuit-breaker |
|||||||
|
|||||||
IL03407011Z (AWA1210-1925) Motor-protective circuit-breaker |
|||||||
|
|||||||
MN03402003Z (AWB1210-1458) PKZM0 motor-protective circuit-breakers, overload monitoring of Ex e motors |
|||||||
|
|||||||
![]() |
EC prototype test certification PTB (German National Institute of Natural and Engineering Sciences) 10 ATEX 3013 | ||||||
![]() |
Schaltvermögen | ||||||
![]() |
Motor starters and "Special Purpose Ratings" for the North American market | ||||||
![]() |
Busbar Component Adapters for modern Industrial control panels |