Datasheet - GST1-AO

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
NH fuse switch-disconnector, 250A, 500V/250A, 690V/200A, size 1
Part no.  GST1-AO
Catalog No.  107250
 
 
Similar to illustration
 

Delivery program
Product range
    60 mm system
Subrange
    NH fuse switch-disconnectors
Description
    Including handguard at top and bottom
Mounting without holes
Function
    For surface mounting on busbars
 
    For fitting on mounting plate
Number of poles
    3 pole
Connection
    Screw M10.
Top
Interval between busbar centres
  mm 60
Rated operational current
Ie A 250
Max. fuse
     
500 V
  A 250
690 V
  A 200
Frame size
    NH1
For use with
    20 x 5/10
25 x 5/10
30 x 5/10
For use with
    Double T profile
Technical data
General
Standards
    IEC/EN 60947-3
Standards
    IEC/EN 60947-3
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
    -25 - +55
Altitude
  m Max. 2000
Interval between busbar centres
  mm 60
Mounting position
    Vertical or horizontal
Overvoltage category/pollution degree
    III/3
Protection type
    IP20 (Operating state)
IP10 (Front cover open)
Direction of incoming supply
    as required
Lifespan, mechanical
Operations   1700
Weight
  kg 4.4
Contacts
Rated operational voltage
Ue V AC 690
Rated operational voltage
Ue V DC 440
Rated operational current
Ie A 250
Rated frequency
f Hz 40 - 60
Rated conditional short-circuit current AC
Iq kAeff 50
Rated conditional short-circuit current, DC
Iq kArms 25
Utilization category AC­22B
     
Rated making capacity
  A 600
Rated breaking capacity
  A 600
Utilization category DC­21B
     
Rated making capacity
  A 300
Rated breaking capacity
  A 300
Lifespan, electrical
Operations   200
Electrical
  Operations 200
Lifespan, mechanical
Operations   1700
Heat dissipation at Ith AC, without NH-SE
  W 8.3
Heat dissipation at Ith DC, without NH-SE
  W 5.5
Rated insulation voltage
Ui V AC 750
Rated impulse withstand voltage
Uimp kV 8
Rated insulation voltage
Ui V 750
Max. fuse
Frame size
    NH1
Max. rated current, gL/gG
  A 250
Max. admissible heat dissipation NH-SE
Pv W 23
Terminal capacity
Flange connection
     
Main cable
d mm M10
Cable lug
  mm2 1 x 25 - 100
Flat busbar
max. mm 30 x 10
Tightening torque
  Nm 30 - 35
Box terminal
     
Stranded copper
  mm2 25 … 150
Copper braid
Lamellenzahl x Breite x Dicke mm 6 x 16 x 0.8
Tightening torque
  Nm 9.5
Clamp-type terminal
     
Stranded aluminium/copper
  mm2 70 … 150
Tightening torque
  Nm 4.5
Double clamp-type terminal
     
Stranded aluminium/copper
  mm2 2 x (70 … 95)
Tightening torque
  Nm 4.5
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 6.0(Show features)(Hide features)
Dimensions