Datasheet - AT4/11-S/I/R316

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Position switch, 1N/O+1N/C, narrow, IP65_x, roller lever
Part no.  AT4/11-S/I/R316
Catalog No.  081181
Eaton Catalog No.  AT4-11-S-I-R316
EL-Nummer (Norway)  4355809

Delivery program
Basic function
    Position switches
Safety position switches
Part group reference
    AT4
Product range
    Rotary lever
Degree of Protection
    IP65
Features
    Complete unit
Ambient temperature
  °C -25 - +70
Design
    EN 50041 Form A
Approval
   
Contacts
     
N/O = Normally open
    1 N/O
N/C = Normally closed
    1 NC
Notes
    = safety function, by positive opening to IEC/EN 60947-5-1
Contact sequence
   
Contact travel■ = Contact closed□ = Contact open
   
Positive opening (ZW)
    yes
Colour
     
Enclosure covers
    Grey
Enclosure covers
   
Housing
    Insulated material
Connection type
    Screw terminal
Notes The operating head can be rotated at 90° intervals to adapt to the specified approach direction.
For degree of protection IP65, use V-M20 (206910) cable glands with connecting thread of max. 9 mm length.
Technical data
General
Standards
    IEC/EN 60947
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Ambient temperature
  °C -25 - +70
Mounting position
    As required
Degree of Protection
    IP65
Terminal capacities
  mm2  
Solid
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Flexible with ferrule
  mm2 1 x (0.5 - 1.5)
2 x (0.5 - 1.5)
Contacts/switching capacity
Rated impulse withstand voltage
Uimp V AC 6000
Rated insulation voltage
Ui V 500
Overvoltage category/pollution degree
    III/3
Rated operational current
Ie A  
AC-15
     
24 V
Ie A 10
220 V 230 V 240 V
Ie A 6
380 V 400 V 415 V
Ie A 4
DC-13
     
24 V
Ie A 10
110 V
Ie A 1
220 V
Ie A 0.5
Supply frequency
  Hz max. 400
Short-circuit rating to IEC/EN 60947-5-1
     
max. fuse
  A gG/gL 6
Repetition accuracy
  mm 0.02
Rated conditional short-circuit current
  kA 1
Mechanical variables
Lifespan, mechanical
Operations x 106 8
Contact temperature of roller head
  °C ≦ 100
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
     
Standard-action contact
  g 5
Snap-action contact
  g 2
Operating frequency
Operations/h   ≦ 6000
Actuation
Mechanical
     
Actuating force at beginning/end of stroke
  N 8.0/20.0
Actuating torque of rotary drives
  Nm 0.3
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 6.0(Show features)(Hide features)